INCORRECT PRESSURE GAUGE ON HIGH PRESSURE SUPPLY LINE
|
Country: UK – Europe |
Location: — |
Incident Date: 3 September 2015 Time: 09:00 |
Type of Activity: Maintenance, inspection, testing |
Type of Injury: Pressure release |
Function: Production |
|
When re-commissioning a Steam Turbine following maintenance, a small steam leak was observed from a pressure gauge located on the high pressure steam supply. The pressure gauge was rated to one Bar(g) and the safety seal failed when it was exposed to 55 Bar(g) steam during re-commissioning. The pressure gauge in question was brand new and had been fitted during the recent maintenance period. |
What Went Wrong?:
- Operations inspected the pressure gauge and found it to be a 0-100% gauge, where a 0-100 Bar pressure gauge should have been installed.
- The 0-100% gauge had been ordered in error for a prior boiler shutdown and had been subsequently stored in the utilities equipment room, rather than returned to the warehouse for disposal.
- Technicians had established a culture of storing some small items in equipment rooms to allow easy access for small maintenance tasks.
- On the day of installation, the 0-100% gauge was mistaken for a 0-100 Bar pressure gauge (due to the near identical appearance) and was taken from the utilities equipment room and installed on the steam turbine high pressure steam supply line. A human error mode of “miss-perception” was recorded following a Human Factors investigation.
Figure 1 – Correct pressure gauge (Bar)

Figure 2 – Incorrect Pressure Gauge (%)
 |
Corrective Actions and Recommendations:
- Check all stores stock to ensure that all pressure gauges are stored in the correct place and in the correct boxes.
- Ensure that all un-used equipment is returned to the place of issue at the end of each day. This ensures that only the correct equipment for a specific work order can be withdrawn.
- Ensure that all pressure gauges are function checked and fit for purpose before installation.
- Review stores stock items and material numbers to establish those that are no longer used or required. Block all numbers that are not required in to prevent re-ordering by accident.
- For legacy assets, review and rationalize all local pressure gauges across each facility with a view to removing those that are no longer used or required.
|
|
Source: https://safetyzone.iogp.org
With a wealth of experience in the oil and gas industry, we provide independent materials and corrosion consultancy to help companies reduce risk, save money and apply best practice in their oil and gas businesses.
Find out more by getting in touch – you’ll get an answer from a qualified, experienced materials engineer every time.
USA toll-free
US: 877-399-1010 (toll free)
UK: +44(0)1144000850
66 Eldon St
Sheffield
S1 4GT
United Kingdom